GOAB SWITCH

 

 

GANG OPERATED AIR BREAK ISOLATING SWITCH [11 kv HEAVY]

Application Click here to view the Image bigger
This product has been designed to suit overhead systems used in high density urban situations or high load centers, where the load current is much higher and the need of improved quality supply is much greater. Main function of this product is to isolate the transformer from distribution system and also used for system isolation from distribution network.

Specification

Type

Outdoor, Single break tilting type.

Mounting

Horizontal / Vertical Mounting.

Standard Specification

IS 9921 1985.

System Voltage

12 / 24 kv, 3 Phase, 50 Hz.

Rated Current

200 / 400 / 630 Amp.

Short Time Current

16 kA for 1 Sec.

Insulation Level

As per IS Standard.

Insulators

320 mm C.D. Porcelain.

Operation

Off Load, Upward-On & Downward-Off.

Isolation

390 mm when contacts are fully open.

Advantage
The angular formation of the contacts & operating mechanism and Handle from channel, results in a very strong arrangement for smooth operation with all operating forces.TOP


GANG OPERATED AIR BREAK ISOLATING SWITCH [11 kv MEDIUM]

Application
This product has been designed with massive low cost electrification programs in rural system and especially Click here to view Image bigger suited for overhead system to isolate the transformer from the distribution system.

Specification

Type

Outdoor, Single break tilting type.

Mounting

Horizontal / Vertical Mounting.

Standard Specification

IS 9921 1985.

System Voltage

12 / 24 kv, 3 Phase, 50 Hz.

Rated Current

200 / 400 Amp.

Short Time Current

10 kA for 1 Sec.

Insulation Level

As per IS Standard.

Insulators

270 mm C.D. Porcelain.

Operation

Off Load, Upward-On & Downward-Off.

Isolation

300 mm when contacts are fully open.


TOP
 

  


DISCONNECTOR LINK

ApplicationClick here to view Image bigger
Disc connector link is a type of isolator switch but is individual phase operated switch. Its operation is achieved by insulated operating rod. Disc connector link has been designed to suit in combined overhead underground network. It is installed at point of tapping from overhead line to underground cable. High standard performance and easy fault location are combined with low installation cost and safety from mischievous operation makes the disc connector link best suitable for overhead network used in high-density urban situation.

Specification

Type

Outdoor, Single break tilting type.

Mounting

Horizontal / Vertical Mounting.

Standard Specification

IS 9921 1985.

System Voltage

12 / 24 kV, 3 Phase, 50 Hz.

Rated Current

200 / 400 / 630 Amp.

Short Time Current

16 kA for 1 Sec.

Insulation Level

As per IS Standard.

Insulators

320 mm C.D. Porcelain.

Operation

Off Load, Upward-On & Downward-Off.

Isolation

390 mm when contacts are fully open.

Advantage
The angular formation of the contacts & operating mechanism and Handle from channel, results in a very strong arrangement for smooth operation with all operating forces.TOP


GANG OPERATED AIR BREAK ISOLATING SWITCH [22 kv HEAVY]

ApplicationClick here to view Image bigger
This product has been designed to suit overhead systems used in high density urban situations or high load centers, where the load current is much higher and the need of improved quality supply is much greater. Main function of this product is to isolate the transformer from distribution system and also used for system isolation from distribution network.

Specification

Type

Outdoor, Single break tilting type.

Mounting

Horizontal / Vertical Mounting.

Standard Specification

IS 9921 1985.

System Voltage

12 / 24 kv, 3 Phase, 50 Hz.

Rated Current

200 / 400 / 630 Amp.

Short Time Current

16 kA for 1 Sec.

Insulation Level

As per IS Standard.

Insulators

320 mm C.D. Porcelain.

Operation

Off Load, Upward-On & Downward-Off.

Isolation

390 mm when contacts are fully open.

Advantage
The angular formation of the contacts & operating mechanism and Handle from channel, results in a very strong arrangement for smooth operation with all operating forces.TOP


GANG OPERATED AIR BREAK ISOLATING SWITCH [22 kv MEDIUM]

ApplicationClick here to view Image bigger
This product has been designed with massive low cost electrification programs in rural system and especially suited for overhead system to isolate the transformer from the distribution system.

Specification

Type

Outdoor, Single break tilting type.

Mounting

Horizontal / Vertical Mounting.

Standard Specification

IS 9921 1985.

System Voltage

12 / 24 kv, 3 Phase, 50 Hz.

Rated Current

200 / 400 Amp.

Short Time Current

10 kA for 1 Sec.

Insulation Level

As per IS Standard.

Insulators

270 mm C.D. Porcelain.

Operation

Off Load, Upward-On & Downward-Off.

Isolation

300 mm when contacts are fully open.

TOP